Store Front Account Search Basket Contents Checkout
Sign In
Order History


Manufacturers
Environmental
Temperature
Level
Pressure
Flow
Sensors & Transmitters
   Data Acquisition
   pH and ORP
   Conductivity
   Relative Humidity / Dewpoint
   Differential Pressure
   Carbon Dioxide
   Nitrogen Dioxide
   Carbon Monoxide
   Smoke Detectors
   Current Sensors
   Proximity Sensors
   Photoelectric Sensors
   Safety Light Curtains
   Cables and Distribution Boxes
   Oxygen Transmitters

 

 

 

 

sales@iprocessmart.com
Tel: 1-925-706-7433



ACI/SL-2000 Smoke Detector (Can be used with Round Ducts)
 
ACI/SL-2000 Smoke Detector (Can be used with Round Ducts)
    Quantity in Basket: None
    Code: ACSL2000
    Price: $230.00
    Shipping Weight: 2.00 pounds
     
     
    Voltage:
    Detection Head:
    Sampling Tube:
    Quantity:
     
    ACI/SM-2000 Smoke Detector
    Automation

    ACI/SL-2000 Smoke Detector

    The ACI/SL-2000 series duct smoke detectors will provide early detection of smoke and products of combustion present in the air moving through a duct in any commercial, industrial, or residential application. These devices are designed for the prevention of smoke re-circulation by the air handling systems, fans, and blowers. Complete systems may be shut down in the event of smoke detection.

    The ACI/SL-2000 will allow up to 30 detectors to be interconnected for some of the common functions including the use of a common test/reset function or to alarm when a single unit alarms. Up to 15 units and signaling devices may be interconnected to operate with a single alarm. The SL-2000 is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors. Output terminals are provided for remote accessories such as horns, strobes, remote status indicators, and test/reset key switches or pushbuttons.

    The Ionization and Photoelectric detector heads are interchangeable. Air sampling is accomplished via two tubes that protrude into the duct. An exhaust tube with a standard length of 7" is supplied in the installation kit with the unit. Once the duct size is determined, a sampling tube must be ordered. Three standard sizes including a 2.5', 5', and 10' lengths can be ordered and cut to the correct size of the duct.

    The ACI/SL-2000 provides (2) sets of 10A Form "C" alarm contacts, along with (1) set of 10A form "C" trouble contacts for monitoring head removal and supply voltage failure. The green pilot and red alarm indicators provided on the front of the SM-501 signal the operating status of the device. The green pilot LED will be extinguished when the detector head is removed. A manual test/reset switch is located next to the LED indicators. All of these units come with a 2 year factory warranty.

    Specifications
    Supply Current
    Voltage Stand-by Alarm
      SM-501 SL-2000 SM-501 SL-2000
    24VAC 35mA 39.3mA 74mA 59.3mA
    24VDC 15mA 13.5mA 56mA 128.7mA
    115VAC 25mA 13.8mA 32mA 27mA
    230VAC 12mA 7.9mA 16mA 16mA
    Air Velocity SM-501 500 to 4,000 ft./min SL-2000 100-4000 ft./min
    Relay Outputs Alarm: (2) sets form "C" relay 10A @ 115 VAC resistive
    Trouble: (1) form "C" relay 10A @ 115 VAC resistive
    Enclosure SL2000: Grey plastic back box, clear plastic cover
    Approvals SL-2000 CSFM Listed (3240-1004:105) / MEA Listed (73-92-E); Vol. 27.
    Ambient Temperature Range SL2000-N: 32 to 155°F (0 to 68°C)
    SL2000-P: 32 to 100°F (0 to 38°C)
    Detector Head SL2000: Series 65
    Wire Size #14 to 22 AWG terminals
    Humidity 10 to 85% RH, non-condensing
    PDF File ACI/SM-2000 Brochure Discounted Pricing available for contractors, resellers and volume purchases
    Contact us at Tel: 925-706-7433 or sales@iprocessmart.com
     