| RTD
Tolerances, Classes and Comparisons |
| Platinum RTD Tolerance Values |
| |
|
|
|
| Temperature
ºC |
Resistance Value
|
Tolerance
DIN-IEC-761 |
Industrial Tolerance Class C
ºC ( )
|
Class
A
ºC( ) |
Class
B
ºC( ) |
-200
-100
0
100
200 |
18.49
60.25
100.00
138.50
175.84 |
±0.55-(±0.24)
±0.35-(±0.14)
±0.15-(±0.06)
±0.35-(±0.13)
±0.55-(±0.20) |
±1.3-(±0.56)
±0.8-(±0.32)
±0.3-(±0.12)
±0.8-(±0.30)
±1.3-(±0.48) |
±2.27
±1.77
±1.27
±1.77
±2.27 |
(±1.15)
(±0.71)
(±0.50)
(±0.67)
(±0.83) |
300
400
500
600
650 |
212.02
247.04
280.90
313.59
329.51 |
±0.75-(±0.27)
±0.95-(±0.33)
±1.15-(±0.38)
±1.35-(±0.43)
±1.45-(±0.46) |
±1.8-(±0.64)
±2.3-(±0.79)
±2.8-(±0.93)
±3.3-(±1.06)
±3.6-(±1.13) |
±2.77
±3.27
±3.77
±4.27
±4.52 |
(±0.98)
(±1.10)
(±1.22)
(±1.32)
(±1.36) |
| RTD
Tolerance Class Definitions |
| DIN |
class
A: ±(0.15 + 0.002 |t|ºC |
 |
Where
t is the actual temperature, in ºC, of the platinum elements. |
| DIN |
class
B: ±(0.30 + 0.005 |t|ºC |
| DIN |
class
C: ±(1.27 + 0.005 |t|ºC |
| RTD Resistance Wire Comparisons |
Element
Metal |
Temperature
Range |
Benefits |
Base
Resistance |
TCR
( / /ºC) |
|
Platinum
|
-436
to 1562ºF
(-260 to 850ºC)
|
Best
stability,
Good linearity
|
100
at 0ºC
|
0.00385
(DIN-IEC-761),
0.003916 (JIS 1604-1981)
|
|
Copper
|
-148
to 500ºF
(-100 to 260ºC)
|
Best
linearity
|
10
at 25ºC
|
0.00427
|
|
Nickel
|
-148
to 500ºF
(-100 to 260ºC)
|
Low
cost,
High Sensitivity
|
120
at 0º C
|
0.00672
|
|
|
| |
|
|
| |
| |
| |