The Series 211 Differential Pressure Transmitter can accurately measure positive, negative, or differential pressure and send the corresponding 4-20 mA output signal. The Series 211 is not position sensitive and can be mounted in any orientation without compromising accuracy. It also features a power LED, so you always know when the transmitter is operating. The compact, lightweight design makes installation simple and easy.
Specifications
Maximum Pressure:
Ranges = 5 PSI -Max 15 PSI
Ranges > 5 PSI -Max 30 PSI
Media compatibility:
Air and compatible non combustible, non corrosive gasses
Accuracy:
Ranges = 4" w.c. 1.0%
Ranges = 5" w.c. 0.25%
Temperature Ranges:
Compensated: 15° to 120°F (-10° to 50°C)
Operating: -10° to 155°F (-25° to 70°C)
Thermal Effect*:
+/- 0.028% FS/°F
Stability:
+/- 0.25% FS/year
Output Signal:
4-20 mA, 2-Wire
Loop Resistance:
250 @ 24 VDC
Power Supply:
12-30 VDC
Housing Material:
ABS Plastic
Electrical Connections:
screw terminals
Process Connection:
Push on connection for 1/8 " tubing
Dimensional Drawings
Model Numbers:
Model Number
Pressure Range
Accuracy
211-D001I-1
0 - 1 "
1%
211-D002I-1
0 - 2 "
1%
211-D004I-1
0 - 4 "
1%
211-D006I-3
0 - 6 "
0.25%
211-D010I-3
0 - 10 "
0.25%
211-D020I-3
0 - 20 "
0.25%
211-D040I-3
0 - 40 "
0.25%
211-D005P-3
0 - 5 PSI
0.25%
211-D010P-3
0 - 10 PSI
0.25%
211-D015P-3
0 - 15 PSI
0.25%
211-Z001I-1
0.5 –0 – 0.5”
1%
211-Z002I-1
1 –0 – 1”
1%
211-Z004I-1
2 –0 – 2”
1%
211-Z010I-3
5 –0 – 5”
0.25%
*Other ranges available upon request.